1910.24
Fixed industrial stairs |
(a) Application of requirements.
This section contains specifications for the safe design and
construction of fixed general industrial stairs. This classification
includes interior and exterior stairs around machinery, tanks,
and other equipment, and stairs leading to or from floors,
platforms, or pits. This section does not apply to stairs
used for fire exit purposes, to construction operations to
private residences, or to articulated stairs, such as may
be installed on floating roof tanks or on dock facilities,
the angle of which changes with the rise and fall of the base
support.
(b) Where fixed stairs are required. Fixed stairs
shall be provided for access from one structure level to another
where operations necessitate regular travel between levels,
and for access to operating platforms at any equipment which
requires attention routinely during operations. Fixed stairs
shall also be provided where access to elevations is daily
or at each shift for such purposes as gauging, inspection,
regular maintenance, etc., where such work may expose employees
to acids, caustics, gases, or other harmful substances, or
for which purposes the carrying of tools or equipment by hand
is normally required. (It is not the intent of this section
to preclude the use of fixed ladders for access to elevated
tanks, towers, and similar structures, overhead traveling
cranes, etc., where the use of fixed ladders is common practice.)
Spiral stairways shall not be permitted except for special
limited usage and secondary access situations where it is
not practical to provide a conventional stairway. Winding
stairways may be installed on tanks and similar round structures
where the diameter of the structure is not less than five
(5) feet.
(c) Stair strength. Fixed stairways shall be designed
and constructed to carry a load of five times the normal live
load anticipated but never of less strength than to carry
safely a moving concentrated load of 1,000 pounds.
(d) Stair width. Fixed stairways shall have a minimum
width of 22 inches.
(e) Angle of stairway rise. Fixed stairs shall be
installed at angles to the horizontal of between 30° and
50° Any uniform combination of rise/tread dimensions may
be used that will result in a stairway at an angle to the
horizontal within the permissible range. Table D-1 gives rise/tread
dimensions which will produce a stairway within the permissible
range, stating the angle to the horizontal produced by each
combination. However, the rise/tread combinations are not
limited to those given in Table D-1.
Table D-1
|
Angle to horizontal |
Rise (in inches) |
Tread run (in inches) |
|
30° 35' |
6 1/2 |
11 |
|
32° 08' |
6 3/4 |
10 3/4 |
|
33° 41' |
7 |
10 1/2 |
|
35° 16' |
7 1/4 |
10 1/4 |
|
36° 52' |
7 1/2 |
10 |
|
38° 29' |
7 3/4 |
9 3/4 |
|
40° 08' |
8 |
9 1/2 |
|
41° 44' |
8 1/4 |
9 1/4 |
|
43° 22' |
8 1/2 |
9 |
|
45° 00' |
8 3/4 |
8 3/4 |
|
46° 38' |
9 |
8 1/2 |
|
48° 16' |
9 1/4 |
8 1/4 |
|
49° 54' |
9 1/2 |
8 |
(f) Stair treads. All treads shall be reasonably
slip-resistant and the nosings shall be of nonslip finish.
Welded bar grating treads without nosings are acceptable providing
the leading edge can be readily identified by personnel descending
the stairway and provided the tread is serrated or is of definite
nonslip design. Rise height and tread width shall be uniform
throughout any flight of stairs including any foundation structure
used as one or more treads of the stairs.
(g) Stairway platforms. Stairway platforms shall
be no less than the width of a stairway and a minimum of 30
inches in length measured in the direction of travel.
(h) Railings and handrails. Standard railings shall
be provided on the open sides of all exposed stairways and
stair platforms. Handrails shall be provided on at least one
side of closed stairways preferably on the right side descending.
Stair railings and handrails shall be installed in accordance
with the provisions of 1910.23.
(i) Vertical clearance. Vertical clearance above
any stair tread to an overhead obstruction shall be at least
7 feet measured from the leading edge of the tread.
|
1910.27 Fixed Ladders |
(a) Design requirements
(1) Design considerations. All ladders, appurtenances,
and fastenings shall be designed to meet the following load
requirements:
(i) The minimum design live load shall be a single concentrated
load of 200 pounds.
(ii) The number and position of additional concentrated
live-load units of 200 pounds each as determined from
anticipated usage of the ladder shall be considered in
the design.
(iii) The live loads imposed by persons occupying the
ladder shall be considered to be concentrated at such
points as will cause the maximum stress in the structural
member being considered.
(iv)The weight of the ladder and attached appurtenances
together with the live load shall be considered in the
design of rails and fastenings.
(b) Specific features
(1) Rungs and cleats.
(i) All rungs shall have a minimum diameter of three-fourths
inch for metal ladders, except as covered in paragraph (i)
of this section and a minimum diameter of 1 1/8 inches for
wood ladders.
(ii) The distance between rungs, cleats, and steps shall not exceed
12 inches and shall be uniform throughout the length of the
ladder.
(iii) The minimum clear length of rungs or cleats shall be 16 inches.
(iv) Rungs, cleats, and steps shall be free of splinters, sharp
edges, burrs, or projections which may be a hazard.
(v) The rungs of an individual-rung ladder shall be so designed
that the foot cannot slide off the end. A suggested design
is shown in figure D-1.
FIGURE D-1. - Suggested design for rungs on individual-rung
ladders.
(2) Side rails. Side rails which might be used as
a climbing aid shall be of such cross sections as to afford
adequate gripping surface without sharp edges, splinters,
or burrs.
(3) Fastenings. Fastenings shall be an integral part
of fixed ladder design.
(4) Splices. All splices made by whatever means shall
meet design requirements as noted in paragraph (a) of this
section. All splices and connections shall have smooth transition
with original members and with no sharp or extensive projections.
(5) Electrolytic action. Adequate means shall be
employed to protect dissimilar metals from electrolytic action
when such metals are joined.
(6) Welding. All welding shall be in accordance with
the "Code for Welding in Building Construction"
(AWSD1.0-1966).
(7) Protection from deterioration.
(i) Metal ladders and appurtenances shall be painted or otherwise
treated to resist corrosion and rusting when location demands.
Ladders formed by individual metal rungs imbedded in concrete,
which serve as access to pits and to other areas under floors,
are frequently located in an atmosphere that causes corrosion
and rusting. To increase rung life in such atmosphere, individual
metal rungs shall have a minimum diameter of 1 inch or shall
be painted or otherwise treated to resist corrosion and rusting.
(iii) When different types of materials are used in the construction
of a ladder, the materials used shall be so treated as to
have no deleterious effect one upon the other.
FIGURE D-2. - Rail Ladder With Bar Steel Rails and Round
Steel
Rungs
(c) Clearance
(1) Climbing side. On fixed ladders, the perpendicular
distance from the centerline of the rungs to the nearest permanent
object on the climbing side of the ladder shall be 36 inches
for a pitch of 76 degrees, and 30 inches for a pitch of 90
degrees (fig. D-2 of this section), with minimum clearances
for intermediate pitches varying between these two limits
in proportion to the slope, except as provided in subparagraphs
(3) and (5) of this paragraph.
(2) Ladders without cages or wells. A clear width
of at least 15 inches shall be provided each way from the
centerline of the ladder in the climbing space, except when
cages or wells are necessary.
(3) Ladders with cages or baskets. Ladders equipped
with cage or basket are excepted from the provisions of subparagraphs
(1) and (2) of this paragraph, but shall conform to the provisions
of paragraph (v) of this section. Fixed ladders in smooth-walled
wells are excepted from the provisions of subparagraph (1)
of this paragraph, but shall conform to the provisions of
paragraph (vi) of this section.
(4) Clearance in back of ladder. The distance from
the centerline of rungs, cleats, or steps to the nearest permanent
object in back of the ladder shall be not less than 7 inches,
except that when unavoidable obstructions are encountered,
minimum clearances as shown in figure D-3 shall be provided.
Minimum Ladder Clearances
FIGURE D-3. - Clearance for Unavoidable Obstruction at Rear
of Fixed Ladder
(5) Clearance in back of grab bar. The distance from
the centerline of the grab bar to the nearest permanent object
in back of the grab bars shall be not less than 4 inches.
Grab bars shall not protrude on the climbing side beyond the
rungs of the ladder which they serve.
(6) Step-across distance. The step-across distance
from the nearest edge of ladder to the nearest edge of equipment
or structure shall be not more than 12 inches, or less than
2 1/2 inches (fig. D-4).
FIGURE D-4. - Ladder Far from Wall
(7) Hatch cover. Counterweighted hatch covers shall
open a minimum of 60 degrees from the horizontal. The distance
from the centerline of rungs or cleats to the edge of the
hatch opening on the climbing side shall be not less than
24 inches for offset wells or 30 inches for straight wells.
There shall be no protruding potential hazards within 24 inches
of the centerline of rungs or cleats; any such hazards within
30 inches of the centerline of the rungs or cleats shall be
fitted with deflector plates placed at an angle of 60 degrees
from the horizontal as indicated in figure D-5. The relationship
of a fixed ladder to an acceptable counterweighted hatch cover
is illustrated in figure D-6.
(d) Special requirements
(1) Cages or wells.
(i) Cages or wells (except on chimney ladders) shall be built,
as shown on the applicable drawings, covered in detail in
figures D-7, D-8, and D-9, or of equivalent construction.
(ii) Cages or wells (except as provided in subparagraph (5) of
this paragraph) conforming to the dimensions shown in figures
D-7, D-8, and D-9 shall be provided on ladders of more than
20 feet to a maximum unbroken length of 30 feet.
FIGURE D-5. - Deflector Plates for Head Hazard
FIGURE D-6. - Relationship of Fixed Ladder to a Safe Access
Hatch
(iii) Cages shall extend a minimum of 42 inches above the top of
landing,unless other acceptable protection is provided.
(iv) Cages shall extend down the ladder to a point not less than
7 feet nor more than 8 feet above the base of the ladder,
with bottom flared not less than 4 inches, or portion of cage
opposite ladder shall be carried to the base.
(v) Cages shall not extend less than 27 nor more than 28 inches
from the centerline of the rungs of the ladder. Cage shall
not be less than 27 inches in width. The inside shall be clear
of projections. Vertical bars shall be located at a maximum
spacing of 40 degrees around the circumference of the cage;
this will give a maximum spacing of approximately 9 1/2 inches,
center to center.
(vi) Ladder wells shall have a clear width of at least 15 inches
measured each way from the centerline of the ladder. Smooth-walled
wells shall be a minimum of 27 inches from the centerline
of rungs to the well wall on the climbing side of the ladder.
Where other obstructions on the climbing side of the ladder
exist, there shall be a minimum of 30 inches from the centerline
of the rungs.
FIGURE D-7. - Cages for Ladders More Than 20 Feet High
FIGURE D-8. - Clearance Diagram for Fixed Ladder in Well
FIGURE D-9. - Cages-Special applications.
(2) Landing platforms. When ladders are used to ascend
to heights exceeding 20 feet (except on chimneys), landing
platforms shall be provided for each 30 feet of height or
fraction thereof, except that, where no cage, well, or ladder
safety device is provided, landing platforms shall be provided
for each 20 feet of height or fraction thereof. Each ladder
section shall be offset from adjacent sections. Where installation
conditions (even for a short, unbroken length) require that
adjacent sections be offset, landing platforms shall be provided
at each offset.
(i) Where a man has to step a distance greater than 12 inches
from the centerline of the rung of a ladder to the nearest
edge of structure or equipment, a landing platform shall be
provided. The minimum step-across distance shall be 2 1/2
inches.
(ii) All landing platforms shall be equipped with standard railings
and toeboards, so arranged as to give safe access to the ladder.
Platforms shall be not less than 24 inches in width and 30
inches in length.
(iii) One rung of any section of ladder shall be located at the
level of the landing laterally served by the ladder. Where
access to the landing is through the ladder, the same rung
spacing as used on the ladder shall be used from the landing
platform to the first rung below the landing.
(3) Ladder extensions. The side rails of through
or side-step ladder extensions shall extend 3 1/2 feet above
parapets and landings. For through ladder extensions, the
rungs shall be omitted from the extension and shall have not
less than 18 nor more than 24 inches clearance between rails.
For side-step or offset fixed ladder sections, at landings,
the side rails and rungs shall be carried to the next regular
rung beyond or above the 3 1/2 feet minimum (fig. D-10).
FIGURE D-10. - Offset Fixed Ladder Sections
(4) Grab bars. Grab bars shall be spaced by a continuation
of the rung spacing when they are located in the horizontal
position. Vertical grab bars shall have the same spacing as
the ladder side rails. Grab-bar diameters shall be the equivalent
of the round-rung diameters.
(5) Ladder safety devices. Ladder safety devices
may be used on tower, water tank, and chimney ladders over
20 feet in unbroken length in lieu of cage protection. No
landing platform is required in these cases. All ladder safety
devices such as those that incorporate lifebelts, friction
brakes, and sliding attachments shall meet the design requirements
of the ladders which they serve.
(e) Pitch
(1) Preferred pitch. The preferred pitch of fixed
ladders shall be considered to come in the range of 75 degrees
and 90 degrees with the horizontal (fig. D-11).
FIGURE D-11. - Pitch of Fixed Ladders
(2) Substandard pitch. Fixed ladders shall be considered
as substandard if they are installed within the substandard
pitch range of 60 and 75 degrees with the horizontal. Substandard
fixed ladders are permitted only where it is found necessary
to meet conditions of installation. This substandard pitch
range shall be considered as a critical range to be avoided,
if possible.
(3) Scope of coverage in this section. This section
covers only fixed ladders within the pitch range of 60 degrees
and 90 degrees with the horizontal.
(4) Pitch greater than 90 degrees. Ladders having
a pitch in excess of 90 degrees with the horizontal are prohibited.
(f) Maintenance. All ladders shall be maintained
in a safe condition. All ladders shall be inspected regularly,
with the intervals between inspections being determined by
use and exposure.
|
1910.29 Manually propelled mobile ladder stands and scaffolds (towers) |
(a) General requirements
(1) Application. This section is intended to prescribe rules and requirements for the design, construction, and use of mobile work platforms (including ladder stands but not including aerial ladders) and rolling (mobile) scaffolds (towers). This standard is promulgated to aid in providing for the safety of life, limb, and property, by establishing minimum standards for structural design requirements and for the use of mobile work platforms and towers.
(2) Working loads.
(i)Work platforms and scaffolds shall be capable of carrying the design load under varying circumstances depending upon the conditions of use. Therefore, all parts and appurtenances necessary for their safe and efficient utilization must be integral parts of the design.
(ii)Specific design and construction requirements are not a part of this section because of the wide variety of materials and design possibilities. However, the design shall be such as to produce a mobile ladder stand or scaffold that will safely sustain the specified loads. The material selected shall be of sufficient strength to meet the test requirements and shall be protected against corrosion or deterioration.
(a)The design working load of ladder stands shall be calculated on the basis of one or more 200-pound persons together with 50 pounds of equipment each.
(b)The design load of all scaffolds shall be calculated on the basis of:
Light - Designed and constructed to carry a working load of 25
pounds per square foot.
Medium - Designed and constructed to carry a working load of 50
pounds per square foot.
Heavy - Designed and constructed to carry a working load of 75
pounds per square foot.
All ladder stands and scaffolds shall be capable of supporting at least four times the design working load.
(iii)The materials used in mobile ladder stands and scaffolds shall be of standard manufacture and conform to standard specifications of strength, dimensions, and weights, and shall be selected to safely support the design working load.
(iv)Nails, bolts, or other fasteners used in the construction of ladders, scaffolds, and towers shall be of adequate size and in sufficient numbers at each connection to develop the designed strength of the unit. Nails shall be driven full length. (All nails should be immediately withdrawn from dismantled lumber.)
(v)All exposed surfaces shall be free from sharp edges, burrs or other safety hazards.
(3) Work levels.
(i) The maximum work level height shall not exceed four (4) times the minimum or least base dimensions of any mobile ladder stand or scaffold. Where the basic mobile unit does not meet this requirement, suitable outrigger frames shall be employed to achieve this least base dimension, or provisions shall be made to guy or brace the unit against tipping.
(ii) The minimum platform width for any work level shall not be less than 20 inches for mobile scaffolds (towers). Ladder stands shall have a minimum step width of 16 inches.
(iii) The supporting structure for the work level shall be rigidly braced, using adequate cross bracing or diagonal bracing with rigid platforms at each work level.
(iv) The steps of ladder stands shall be fabricated from slip resistant treads.
(v) The work level platform of scaffolds (towers) shall be of wood, aluminum, or plywood planking, steel or expanded metal, for the full width of the scaffold, except for necessary openings. Work platforms shall be secured in place. All planking shall be 2-inch (nominal) scaffold grade minimum 1,500 f. (stress grade) construction grade lumber or equivalent.
(vi) All scaffold work levels 10 feet or higher above the ground or floor shall have a standard (4-inch nominal) toeboard.
(vii) All work levels 10 feet or higher above the ground or floor shall have a guardrail of 2- by 4-inch nominal or the equivalent installed no less than 36 inches or more than 42 inches high, with a mid-rail, when required, of 1- by 4-inch nominal lumber or equivalent.
(viii) A climbing ladder or stairway shall be provided for proper access and egress, and shall be affixed or built into the scaffold and so located that its use will not have a tendency to tip the scaffold. A landing platform shall be provided at intervals not to exceed 30 feet.
(4) Wheels or casters.
(i) Wheels or casters shall be properly designed for strength and dimensions to support four (4) times the design working load.
(ii) All scaffold casters shall be provided with a positive wheel and/or swivel lock to prevent movement. Ladder stands shall have at least two (2) of the four (4) casters and shall be of the swivel type.
(iii) Where leveling of the elevated work platform is required, screw jacks or other suitable means for adjusting the height shall be provided in the base section of each mobile unit.
(b) Mobile tubular welded frame scaffold
(1) General. Units shall be designed to comply with the requirements of paragraph (a) of this section.
(2) Bracing. Scaffolds shall be properly braced by cross braces and/or diagonal braces for securing vertical members together laterally. The cross braces shall be of a length that will automatically square and align vertical members so the erected scaffold is always plumb, square, and rigid.
(3) Spacing. Spacing of panels or frames shall be consistent with the loads imposed. The frames shall be placed one on top of the other with coupling or stacking pins to provide proper vertical alignment of the legs.
(4) Locking. Where uplift may occur, panels shall be locked together vertically by pins or other equivalent means.
(5) Erection. Only the manufacturer of a scaffold or his qualified designated agent shall be permitted to erect or supervise the erection of scaffolds exceeding 50 feet in height above the base, unless such structure is approved in writing by a registered professional engineer, or erected in accordance with instructions furnished by the manufacturer.
(c) Mobile tubular welded sectional folding scaffolds
(1) General. Units including sectional stairway and sectional ladder scaffolds shall be designed to comply with the requirements of paragraph (a) of this section.
(2) Stairway. An integral stairway and work platform shall be incorporated into the structure of each sectional folding stairway scaffold.
(3) Bracing. An integral set of pivoting and hinged folding diagonal and horizontal braces and a detachable work platform shall be incorporated into the structure of each sectional folding ladder scaffold.
(4) Sectional folding stairway scaffolds. Sectional folding stairway scaffolds shall be designed as medium duty scaffolds except for high clearance. These special base sections shall be designed as light duty scaffolds. When upper sectional folding stairway scaffolds are used with a special high clearance base, the load capacity of the entire scaffold shall be reduced accordingly. The width of a sectional folding stairway scaffold shall not exceed 4 1/2 feet. The maximum length of a sectional folding stairway scaffold shall not exceed 6 feet.
(5) Sectional folding ladder scaffolds. Sectional folding ladder scaffolds shall be designed as light duty scaffolds including special base (open end) sections which are designed for high clearance. For certain special applications the six-foot (6') folding ladder scaffolds, except for special high clearance base sections, shall be designed for use as medium duty scaffolds. The width of a sectional folding ladder scaffold shall not exceed 4 1/2 feet. The maximum length of a sectional folding ladder scaffold shall not exceed 6 feet 6 inches for a six-foot (6') long unit, 8 feet 6 inches for an eight-foot (8') unit or 10 feet 6 inches for a ten-foot (10') long unit.
(6) End frames. The end frames of sectional ladder and stairway scaffolds shall be designed so that the horizontal bearers provide supports for multiple planking levels.
(7) Erection. Only the manufacturer of the scaffold or his qualified designated agent shall be permitted to erect or supervise the erection of scaffolds exceeding 50 feet in height above the base, unless such structure is approved in writing by a licensed professional engineer, or erected in accordance with instructions furnished by the manufacturer.
(d) Mobile tube and coupler scaffolds
(1) Design. Units shall be designed to comply with the applicable requirements of paragraph (a) of this section.
(2) Material. The material used for the couplers shall be of a structural type, such as a drop-forged steel, malleable iron or structural grade aluminum. The use of gray cast iron is prohibited.
(3) Erection. Only the manufacturer of the scaffold or his qualified designated agent shall be permitted to erect or supervise the erection of scaffolds exceeding 50 feet in height above the base, unless such structure is approved in writing by a licensed professional engineer, or erected in accordance with instructions furnished by the manufacturer.
(e) Mobile work platforms
(1) Design. Units shall be designed for the use intended and shall comply with the requirements of paragraph (a) of this section.
(2) Base width. The minimum width of the base of mobile work platforms shall not be less than 20 inches.
(3) Bracing. Adequate rigid diagonal bracing to vertical members shall be provided.
(f) Mobile ladder stands
(1) Design. Units shall comply with applicable requirements of paragraph (a) of this section.
(2) Base width. The minimum base width shall conform to paragraph (i) of this section. The maximum length of the base section shall be the total length of combined steps and top assembly, measured horizontally, plus five-eighths inch per step of rise.
(3) Steps. Steps shall be uniformly spaced, and sloped, with a rise of not less than nine (9) inches, nor more than ten (10) inches, and a depth of not less seven (7) inches. The slope of the steps section shall be a minimum of fifty-five (55) degrees and a maximum of sixty (60) degrees measured from the horizontal.
(4) Handrails.
(i) Units having more than five (5) steps or 60 inches vertical height to the top step shall be equipped with handrails.
(ii) Handrails shall be a minimum of 29 inches high. Measurements shall be taken vertically from the center of the step.
(5) Loading. The load (see paragraph (a) of this section) shall be applied uniformly to a 3 1/2 inches wide area front to back at the center of the width span with a safety factor of four (4).
|
|